Process lines and machines: what to measure, and where it goes.

Ovens, smokehouses, slicers, extruders, conveyors, blow molders and the rooms around them in food, feed and plastics plants.

Oven or dryer

Zone or exhaust temperature

Sound familiar? “When a batch goes wrong, we can’t see what the oven was doing.”

Sensors
Where it goesProbe through an existing port into each zone’s air stream, or into the exhaust duct; the transmitter outside the heat, within the probe lead.
How it mountsCompression fitting in a port; never on a heated barrel or a surface hotter than the node allows.
How manyOne per zone
What it readsTemperature to 500 °C (No. 09), 800 °C (No. 10) or 375 °C by thermocouple (No. 48)
What it catchesBurner or element faults, airflow loss, profile drift
What you getTemperature history by zone when a batch goes wrong
Pairs with
Add No. 09 to a plan →

Smokehouse (meat)

Circulation-fan vibration

Sensor
Where it goesFan motor bearings outside the chamber; shaft bearings with a thermal standoff where the surface runs above 80 °C.
How it mountsStud mount is best; an epoxy pad where drilling isn’t allowed; a flat magnet on flat, bare steel only. Clean to bare metal and mark the axes. Plan earlier battery changes in the heat.
How manyOne per machine to start. Large or critical machines can take one at each main bearing; an engineer sets the count at the assessment.
What it readsVibration velocity (mm/s), acceleration and peak (g), kurtosis and crest factor; surface temperature (°C)
What it catchesImbalance, misalignment, looseness, bearing wear and lubrication problems
What you getEarly warning of a developing fault, so the repair is planned for downtime instead of forced by a stop
Add No. 05 to a plan →

Slicer

Vibration

Sensor
Where it goesDrive motor drive-end bearing and the gearbox or spindle bearing housing, away from the blade guards.
How it mountsStud mount is best; an epoxy pad where drilling isn’t allowed; a flat magnet on flat, bare steel only. Clean to bare metal and mark the axes. Install with the machine locked out unless the magnet can go on from outside the guard. The node is IP66; plan for washdown.
How manyOne per machine to start. Large or critical machines can take one at each main bearing; an engineer sets the count at the assessment.
What it readsVibration velocity (mm/s), acceleration and peak (g), kurtosis and crest factor; surface temperature (°C)
What it catchesImbalance, misalignment, looseness, bearing wear and lubrication problems
What you getEarly warning of a developing fault, so the repair is planned for downtime instead of forced by a stop
Add No. 05 to a plan →

Brine pump

Vibration

Sensor
Where it goesPump bearing housings (not the volute) and the motor drive-end bearing.
How it mountsStud mount is best; an epoxy pad where drilling isn’t allowed; a flat magnet on flat, bare steel only. Clean to bare metal and mark the axes. Install with the machine locked out unless the magnet can go on from outside the guard.
How manyOne per machine to start. Large or critical machines can take one at each main bearing; an engineer sets the count at the assessment.
What it readsVibration velocity (mm/s), acceleration and peak (g), kurtosis and crest factor; surface temperature (°C)
What it catchesImbalance, misalignment, looseness, bearing wear and lubrication problems; cavitation
What you getEarly warning of a developing fault, so the repair is planned for downtime instead of forced by a stop
Add No. 05 to a plan →

Extruder (pet food, feed)

Gearbox and motor vibration, and barrel data

Sensors
Where it goesVibration on the main motor drive end and the gearbox input and output bearing caps; barrel temperatures and load read from the PLC over Modbus.
How it mountsStud mount is best; an epoxy pad where drilling isn’t allowed; a flat magnet on flat, bare steel only. Clean to bare metal and mark the axes. Modbus only with the controls team’s approval.
How manyOne vibration sensor per extruder to start, plus one Modbus bridge
What it readsVibration velocity (mm/s), acceleration and peak (g), kurtosis and crest factor; surface temperature (°C); PLC registers
What it catchesImbalance, misalignment, looseness, bearing wear and lubrication problems; gearbox wear
What you getEarly warning of a developing fault, so the repair is planned for downtime instead of forced by a stop
Add No. 05 to a plan →

Conveyor (belt or chain)

Drive vibration and current

Sound familiar? “Conveyors always seem to break at midnight, right when volume peaks.”

Sensors
Where it goesDrive motor drive end and the drive gearbox bearing caps; head-pulley bearings; three-phase clamps in the starter for jams and overload.
How it mountsStud mount is best; an epoxy pad where drilling isn’t allowed; a flat magnet on flat, bare steel only. Clean to bare metal and mark the axes. Install with the machine locked out unless the magnet can go on from outside the guard.
How manyOne vibration sensor and one current meter per drive to start
What it readsVibration velocity (mm/s), acceleration and peak (g), kurtosis and crest factor; surface temperature (°C); current per phase
What it catchesImbalance, misalignment, looseness, bearing wear and lubrication problems; jams (a current spike)
What you getLets maintenance plan the repair for a quiet shift instead of a breakdown at peak load
Add No. 05 to a plan →

Grain cleaning, sizing and bagging line

Bearing vibration

Sensor
Where it goesBearings on the cleaner, sizer and bagger drives, at the positions for each machine type.
How it mountsStud mount is best; an epoxy pad where drilling isn’t allowed; a flat magnet on flat, bare steel only. Clean to bare metal and mark the axes.
How manyOne per drive to start
What it readsVibration velocity (mm/s), acceleration and peak (g), kurtosis and crest factor; surface temperature (°C)
What it catchesImbalance, misalignment, looseness, bearing wear and lubrication problems
What you getEarly warning of a developing fault, so the repair is planned for downtime instead of forced by a stop
Add No. 05 to a plan →

Pendulum machine

Main-bearing vibration

Sensor
Where it goesOn its two main bearings.
How it mountsStud mount is best; an epoxy pad where drilling isn’t allowed; a flat magnet on flat, bare steel only. Clean to bare metal and mark the axes.
How manyOne per machine to start. Large or critical machines can take one at each main bearing; an engineer sets the count at the assessment.
What it readsVibration velocity (mm/s), acceleration and peak (g), kurtosis and crest factor; surface temperature (°C)
What it catchesBearing wear from too much or too little grease
What you getEarly warning of a developing fault, so the repair is planned for downtime instead of forced by a stop
Add No. 05 to a plan →

Food production room (ready-to-eat)

Room temperature, humidity and dew point

Sensor
Where it goesMagnet-mount on a wall or column in the room, away from doors and sanitation spray.
How it mountsMagnet; IP67.
How manyOne or two per room
What it readsTemperature and relative humidity; dew point calculated
What it catchesCondensation, which food-safety programs work to control
What you getA dew-point record for rooms where condensation matters
Add No. 27 to a plan →

Odor-producing room (slurry, rendering)

Odorous gases indoors and at the exhaust

Sensors
Where it goesOne air station in the room and one at the exhaust stack, with gas cells chosen for the odorants.
How it mountsWall or ceiling indoors; weather-rated outdoors; AC or DC power.
How manyOne indoor and one exhaust station per room, plus one in an untreated room for comparison
What it readsGas-cell readings for the chosen odorants, particulates, temperature and humidity
What it catchesHow odor control is performing; seasonal swings that can mislead
What you getA before-and-after reading of odor treatment at the stack
Pairs with
Add No. 136 to a plan →

Blow molding machine

Drive, pump and gearbox vibration

Sound familiar? “When a blow molder stops, the whole bottle line stops.”

Sensor
Where it goesHydraulic pump, extruder drive and gearbox bearings; never on heated barrels.
How it mountsBolted or bonded on. Install with the machine locked out unless a magnet can go on from outside the guard.
How manyOne per machine to start. Large or critical machines can take one at each main bearing; an engineer sets the count at the assessment.
What it readsVibration velocity (mm/s), acceleration and peak (g), kurtosis and crest factor; surface temperature (°C)
What it catchesImbalance, misalignment, looseness, bearing wear and lubrication problems; overheating
What you getEarly warning of a developing fault, so the repair is planned for downtime instead of forced by a stop
Add No. 05 to a plan →

Main power feed

Sensor
Where it goesThree-phase clamp-on on the machine’s main feed.
How it mountsAn electrician installs.
How manyOne per machine
What it readsCurrent per phase; run, idle and off hours by shift
What it catchesMachines idling under power
What you getRun, idle and off hours for every machine
Add No. 15 to a plan →

Mold cooling supply and return

Sensors
Where it goesFlow meter in-line on the mold cooling supply; temperature probes on the supply and return; pipe pressure on the supply.
How it mountsIn-line fittings go in during a planned stop.
How manyOne flow meter, one two-probe transmitter and one pressure sensor per circuit
What it readsFlow (L/min), temperature at two points, pressure
What it catchesCooling problems that stretch cycle time
What you getCatches the cooling drift that stretches cycle time
Pairs with
Add No. 19 to a plan →

Process chiller or tower water (plastics)

Conductivity

Sensor
Where it goesA water-quality converter with a conductivity probe in the chiller or tower loop.
How it mountsProbe in a flow cell or tank.
How manyOne per loop
What it readsConductivity
What it catchesDissolved solids building up; scale risk
Pairs with
Add No. 35 to a plan →

Plant air or blow-air header (plastics)

Header pressure

Sensor
Where it goesPipe pressure at the blow-air header and at the plant air drop to the machine.
How it mountsThreads into the line during a stop.
How manyOne or two per machine
What it readsGauge pressure, 0 to 16 bar (232 psi)
What it catchesPressure lost to drops and leaks between the compressor and the machine
Add No. 22 to a plan →

Placement and quantities are starting points from Cognituv’s install guidance. A Cognituv engineer confirms them for your site, and the product data sheet governs. Electrical and hazardous-area work follows the site’s own rules and permits.

All asset groups →Ask an engineer about your equipment →

Have an equipment list?

Upload it in the planner. It suggests what to measure on each asset and a gateway to carry it, and a Cognituv engineer confirms the plan.

Prefer to talk? Call 1-888-580-8738

Plan your system