Compressed air: what to measure, and where it goes.
Compressor power and temperature, header pressure and the pressure lost across filters and dryers.
Air compressor (rotary screw)
Power and load or unload cycling
Sound familiar? “Why is the compressor running when nothing’s in production?”
| Sensors | |
|---|---|
| Where it goes | Three-phase clamps on the compressor feeder, or kW and status read from the compressor controller over Modbus. |
| How it mounts | An electrician fits the clamps; Modbus only with the plant controls team’s approval. |
| How many | One per compressor |
| What it reads | Current per phase and amp-hours, or the controller’s kW, load and hours |
| What it catches | Leaks running the compressor overnight; poor sequencing |
| What you get | Shows what the air system costs with the line down |
| Pairs with |
Discharge and aftercooler temperature
| Sensor | |
|---|---|
| Where it goes | Waterproof PT100 probes on the compressor discharge line and the aftercooler outlet. |
| How it mounts | Strap-on or in an existing well; the transmitter on a wall. |
| How many | One two-probe transmitter per compressor |
| What it reads | Temperature at two points (°C) |
| What it catches | Overheating, a fouled cooler, low oil |
| What you get | A health trend on the compressor itself |
| Pairs with |
Compressed-air header
Header pressure
Sound familiar? “By second shift, the pressure at the end of the line drops off.”
| Sensors | |
|---|---|
| Where it goes | At the header leaving the receiver or dryer, and at the far end of the distribution loop (the last drop), each with an isolation valve. |
| How it mounts | 1/4-in. NPT, on an existing tap or fitted during a planned stop. |
| How many | Two per system: the start and the end of the header |
| What it reads | Gauge pressure |
| What it catches | Pressure lost along the header; leaks, from an off-shift decay test |
| What you get | A before-and-after record for leak repairs, and the pressure at the point of use |
| Pairs with |
Compressed-air filters and dryer
Pressure drop
| Sensor | |
|---|---|
| Where it goes | Ports on each side of the filter, dryer or separator. |
| How it mounts | 1/8-in. NPT, two ports; the housing is IP66 for outdoor use. |
| How many | One per filter or dryer |
| What it reads | Differential pressure (air or gas) and temperature |
| What it catches | Loaded filters, a failing dryer |
| What you get | Filter changes on condition, and less pressure lost before the line |
Placement and quantities are starting points from Cognituv’s install guidance. A Cognituv engineer confirms them for your site, and the product data sheet governs. Electrical and hazardous-area work follows the site’s own rules and permits.
Have an equipment list?
Upload it in the planner. It suggests what to measure on each asset and a gateway to carry it, and a Cognituv engineer confirms the plan.