Compressed air: what to measure, and where it goes.

Compressor power and temperature, header pressure and the pressure lost across filters and dryers.

Air compressor (rotary screw)

Power and load or unload cycling

Sound familiar? “Why is the compressor running when nothing’s in production?”

Sensors
Where it goesThree-phase clamps on the compressor feeder, or kW and status read from the compressor controller over Modbus.
How it mountsAn electrician fits the clamps; Modbus only with the plant controls team’s approval.
How manyOne per compressor
What it readsCurrent per phase and amp-hours, or the controller’s kW, load and hours
What it catchesLeaks running the compressor overnight; poor sequencing
What you getShows what the air system costs with the line down
Pairs with
Add No. 08 to a plan →

Discharge and aftercooler temperature

Sensor
Where it goesWaterproof PT100 probes on the compressor discharge line and the aftercooler outlet.
How it mountsStrap-on or in an existing well; the transmitter on a wall.
How manyOne two-probe transmitter per compressor
What it readsTemperature at two points (°C)
What it catchesOverheating, a fouled cooler, low oil
What you getA health trend on the compressor itself
Pairs with
Add No. 11 to a plan →

Compressed-air header

Header pressure

Sound familiar? “By second shift, the pressure at the end of the line drops off.”

Sensors
Where it goesAt the header leaving the receiver or dryer, and at the far end of the distribution loop (the last drop), each with an isolation valve.
How it mounts1/4-in. NPT, on an existing tap or fitted during a planned stop.
How manyTwo per system: the start and the end of the header
What it readsGauge pressure
What it catchesPressure lost along the header; leaks, from an off-shift decay test
What you getA before-and-after record for leak repairs, and the pressure at the point of use
Pairs with
Add No. 17 to a plan →

Compressed-air filters and dryer

Pressure drop

Sensor
Where it goesPorts on each side of the filter, dryer or separator.
How it mounts1/8-in. NPT, two ports; the housing is IP66 for outdoor use.
How manyOne per filter or dryer
What it readsDifferential pressure (air or gas) and temperature
What it catchesLoaded filters, a failing dryer
What you getFilter changes on condition, and less pressure lost before the line
Add No. 18 to a plan →

Placement and quantities are starting points from Cognituv’s install guidance. A Cognituv engineer confirms them for your site, and the product data sheet governs. Electrical and hazardous-area work follows the site’s own rules and permits.