Radar level
| Device | Measures | Range | Accuracy | Radio | Mount | Rating | Power |
|---|---|---|---|---|---|---|---|
| No. 21 Radar level sensor | Distance to surface; level | 0.3–12 m; ±2 mm typical (up to ±5 mm); 1 mm resolution | Not listed | Not listed | Top of the vessel on a 1½-inch G or NPT tank thread, or a wall bracket; 8° beam | IP68; −40 to 70 °C operating | Battery, about 5 years |
| No. 110 Radar distance sensor, 20 m | Distance to the surface, converted to level | 0.5 to 20 m; 78° beam; 1 cm resolution | ±0.1 m | LoRaWAN (North America) | Above the tank, sewer or bin, facing down | −20 to 85 °C operating | Lithium battery; about 5 years (manufacturer rating) |
| No. 111 Cellular radar tank level sensor | Distance to the liquid surface, converted to level; location (GPS) | 0.1 to 6.75 m; 8° beam; 2 mm resolution | Through a port: ±4 mm to 2 m, ±0.75% FS from 2 to 4 m, ±2% FS beyond; non-invasive: ±2% FS | Cellular (LTE-M or NB-IoT) | 2 in adapter, or optional non-invasive adhesive-pad adapter | IP68; −25 to 50 °C operating | Lithium battery; about 10 years (manufacturer rating) |
Ultrasonic and laser level and distance
| Device | Measures | Range | Accuracy | Radio | Mount | Rating | Power |
|---|---|---|---|---|---|---|---|
| No. 91 Laser silo & tank level sensor | Distance to the surface, converted to level | Up to 40 m | ±50 mm under 2 m; ±1% of distance or ±25 mm from 2 m | LoRaWAN (North America) | Above the tank or silo, facing down | IP67; −20 to 50 °C operating | Alkaline batteries; about 8 years (manufacturer rating) |
| No. 92 Ultrasonic water & wastewater level sensor | Distance to the liquid surface, converted to level | Not listed | ±1% or better (factory calibrated) | LoRaWAN (North America) | Above the tank or sump, facing down, at least 0.3 m above the highest liquid level | IP67; −20 to 50 °C operating | Alkaline batteries; about 7 years (manufacturer rating) |
| No. 93 Waste bin fill sensor | Fill height, temperature and tilt | 0.15 to 4 m | Height ±3 cm; temperature ±2 °C; tilt ±2° | LoRaWAN (North America) | Top cover or side mount with bracket | IP68; −30 to 85 °C operating | Lithium battery; about 3 years (manufacturer rating) |
| No. 94 Ultrasonic distance sensor, 4.5 or 7.5 m | Distance to the surface, converted to level | 30 mm to 4.5 m or 0.28 to 7.5 m | ±(1 cm + 0.3% of distance) | LoRaWAN (North America) | Above a flat liquid or solid surface, probe facing it; 60° beam (4.5 m) or 40° beam (7.5 m) | IP66; −40 to 85 °C operating | Lithium battery; about 5 years (manufacturer rating) |
| No. 95 Short-range laser distance sensor | Distance to the nearest object or surface | 3 cm to 2 m | ±2 cm from 3 cm to 1 m; ±5% from 1 to 2 m | LoRaWAN (North America) | Facing the target, 3 cm to 2 m away; 18° beam | Indoor; −40 to 80 °C operating | Battery or DC |
| No. 96 Four-channel ultrasonic distance sensor | Distance at up to four points, converted to level | Not listed | ±(1 cm + 0.3% of distance) | LoRaWAN (North America) | Node nearby; each probe above its surface, facing down | IP67 | Lithium battery |
| No. 97 Narrow-beam laser level sensor, 12 or 40 m | Distance to the surface, converted to level | 0.1 to 12 m or 0.1 to 40 m | 12 m version: ±5 cm from 0.1 to 5 m; ±1% from 5 to 12 m | LoRaWAN (North America) | Above the surface, probe facing down; 3.6° beam (12 m) or 3° beam (40 m) | IP65; −40 to 85 °C operating | Lithium battery; about 5 years (manufacturer rating) |
| No. 98 Cellular ultrasonic distance sensor | Distance to the surface, converted to level | 0.28 to 7.5 m | ±(1 cm + 0.3% of distance) | Cellular (LTE or NB-IoT), SIM included | Above a flat liquid or solid surface, probe facing it | IP66; −40 to 85 °C operating | Lithium battery; about 5 years (manufacturer rating) |
| No. 99 Corrosion-resistant ultrasonic level sensor | Distance to the surface, converted to level | Up to 10 m | Not listed | LoRaWAN (North America) | Above the tank, facing the liquid | IP68; parylene-coated transducer, POM housing; −20 to 85 °C operating | Lithium battery; about 10 years (manufacturer rating) |
| No. 100 Ultrasonic pit & tank level sensor | Distance to the surface, converted to level | Up to 5 m | Not listed | LoRaWAN (North America) | Above the tank or pit, facing the liquid | IP65; −20 to 85 °C operating | Lithium battery; about 10 years (manufacturer rating) |
| No. 101 Compact ultrasonic distance sensor | Distance to the contents, converted to level | 3 cm to 4.5 m | ±(1 cm + 0.3% of distance); 1 mm resolution | LoRaWAN (North America) | Surface mount with screws, facing the target; 60° beam | IP67; −15 to 60 °C operating | Lithium battery; about 10 years (manufacturer rating) |
| No. 102 Multi-purpose ultrasonic distance sensor | Distance, fill level and temperature | 3 cm to 4.5 m; 60° beam | Not listed | LoRaWAN (North America) | Surface mount with screws | IP67; −30 to 70 °C operating | Lithium battery; about 10 years (manufacturer rating) |
| No. 103 Weatherproof laser distance sensor | Distance, fill level and temperature | 2 cm to 3.5 m; 27° beam; 1 mm resolution | ±2 cm (−20 to 70 °C) | LoRaWAN (North America) | Surface mount with screws, facing the target | IP67; −30 to 70 °C operating | Lithium battery; about 10 years (manufacturer rating) |
| No. 104 Container fill-level sensor | Distance to the contents, converted to fill level | 1 to 55 cm | ±1 cm | LoRaWAN (North America) | Adhesive tape inside the container | IP30, indoor; −10 to 60 °C operating | Lithium battery; about 2 years (manufacturer rating) |
| No. 105 Ultrasonic level sensor, 5 or 10 m | Distance to the surface, level and temperature | Up to 5 m or 10 m, by version | ±(1 cm + 0.3% of distance) | LoRaWAN (North America) | Surface mount with screws, above the target | IP67; −30 to 70 °C operating | Lithium battery; about 10 years (manufacturer rating) |
| No. 106 Threaded tank level monitor | Liquid level and temperature | Up to 5.8 m | Not listed | LoRaWAN (North America) | Threads into a 1 in NPT tank port | IP67; −40 to 60 °C operating | Battery; about 5 years (manufacturer rating) |
| No. 107 Intrinsically safe tank level monitor | Liquid level and temperature | Up to 3 m | Not listed | LoRaWAN (North America) | Threads into a 1 in NPT tank port | IP67; −40 to 60 °C operating | Battery; about 5 years (manufacturer rating) |
| No. 108 Fuel & water tank level sensor | Distance to the liquid surface, converted to level | 0.12 to 4 m; 30° beam | ±2 cm typical | LoRaWAN (North America) | Threads into a 2 in BSP port on the tank top | IP67; −20 to 50 °C operating | Lithium battery; about 14 years (manufacturer rating) |
Submersible, pressure and capacitive level
All 9Radio: LoRaWAN (North America)
| Device | Measures | Accuracy | Mount | Rating | Power |
|---|---|---|---|---|---|
| No. 83 Submersible level & temperature probe, 10 m | Liquid level (hydrostatic pressure) and liquid temperature | ±0.5% FS total error band; 0.3 mm resolution; temperature ±2 °C typical | Cable-suspended 316L stainless probe, 10 m cable | IP68; −20 to 50 °C operating | Alkaline batteries; about 11 years (manufacturer rating) |
| No. 84 High-precision submersible level & temperature probe | Liquid level (hydrostatic pressure) and liquid temperature | Pressure ±0.1% FS total error band; temperature ±0.3 °C | Cable-suspended 316L stainless probe, 10 m cable | IP68; −20 to 50 °C operating | Alkaline batteries; about 10 years (manufacturer rating) |
| No. 85 Submersible tank level transmitter with temperature | Liquid level (hydrostatic pressure) and temperature | ±0.25% of span, typical | Cable-suspended 304/316 stainless probe, no process connection | IP68; −20 to 85 °C operating | Lithium battery; about 10 years (manufacturer rating) |
| No. 86 Corrosive liquid level transmitter | Liquid level (hydrostatic pressure) | ±0.25% of span, typical | Cable-suspended probe, no process connection | IP68; −20 to 85 °C operating | Lithium battery; about 10 years (manufacturer rating) |
| No. 87 Low-power submersible level transmitter | Liquid level (hydrostatic pressure) | ±0.25% of span, typical | Cable-suspended probe, no process connection | Not listed | Lithium battery; about 10 years (manufacturer rating) |
| No. 88 Submersible level transmitter, 1 m cable | Liquid level (hydrostatic pressure) | ±0.25% of span, typical | Cable-suspended probe, 1 m cable | IP68; −20 to 85 °C operating | Lithium battery; about 10 years (manufacturer rating) |
| No. 89 Capacitive level sensor | Liquid level at the electrode pad | Not listed | Adhesive electrode pad on the tank wall | IP67; indoor use | Lithium battery |
| No. 90 Submersible water level sensor | Water level (hydrostatic pressure) | ±0.5% FS; 0.01 m resolution | Cable-suspended 304 stainless probe | IP68; −30 to 70 °C operating | Lithium battery; about 10 years (manufacturer rating) |
| No. 109 Thread-in level & temperature sensor | Hydrostatic pressure, converted to liquid level; liquid temperature | ±0.7% FS total error band; temperature ±2 °C typical | Threads into a 1/4 in NPT tank port; 2 m cable to the radio unit | IP67; −20 to 50 °C operating | Alkaline batteries; about 10 years (manufacturer rating) |
Pressure, tilt and position
| Device | Measures | Range | Mount | Rating | Power |
|---|---|---|---|---|---|
| No. 22 Pipe pressure sensor, 0–16 bar | Gauge pressure, liquid or gas | 0–16 bar | Probe threads into the line; transceiver on a 1.5 m cable mounts on a wall, pole or DIN rail | IP65; −10 to 70 °C operating | Battery, about 10 years (manufacturer rating) |
| No. 23 Differential pressure, rooms & filters | Differential pressure; temperature; humidity | Not listed | Wall, with tubing to each side | Indoor | Battery |
| No. 24 Tilt & position sensor | Tilt angle on three axes; movement events | ±90°; ±1° | Bolt or adhesive on the structure | IP67; −30 to 60 °C operating | Battery, about 3 years |
Temperature probes
All 6Radio: LoRaWAN (North America)
| Device | Measures | Range | Accuracy | Inputs | Mount | Rating | Power |
|---|---|---|---|---|---|---|---|
| No. 25 Food-safety temperature, 2-channel | Temperature on two probes | −40 to 260 °C probe; ±0.5 °C (0–80 °C), Class A PT100 | Not listed | Not listed | Probes in the tank or room; transmitter outside the washdown zone (−40 to 65 °C) | Food-safety type, IP65 transmitter | Lithium battery |
| No. 26 Ultra-low PT100 probe, −196 °C | Temperature on two probes | −196 to 150 °C; ±0.5 °C (0–80 °C) | Not listed | Not listed | Wall transmitter; 2 m probe leads | Transmitter −40 to 65 °C | Lithium battery |
| No. 78 Long-reach temperature probe | Temperature | −55 to 125 °C | Better than ±0.5 °C from −10 to 85 °C | One temperature probe on a 5 m cable | Not listed | IP67; node operates −20 to 50 °C | Alkaline batteries, about 11.6 years (manufacturer rating) |
| No. 80 Insertion temperature sensor | Temperature | −30 to 70 °C | ±0.5 °C typical | 316 stainless steel insertion probe | Not listed | IP67 | Lithium battery, about 10 years (manufacturer rating) |
| No. 81 Temperature probe node with display | Temperature from PT100 probes; door open or closed on a channel | Not listed | Not listed | One or two PT100 probe channels; a channel can take a door contact | Wall or magnet | IP65; operates −30 to 70 °C | Battery or DC |
| No. 82 Multi-point HVAC temperature node | Temperature at three points | −55 to 125 °C | ±0.5 °C (−10 to 85 °C); 0.1 °C resolution | Three temperature probes on 1 m leads | Not listed | Not listed | Lithium battery, about 3 years (manufacturer rating) |
Temperature and humidity
All 6Radio: LoRaWAN (North America)
| Device | Measures | Range | Accuracy | Mount | Rating | Power |
|---|---|---|---|---|---|---|
| No. 27 Magnet-mount temperature & humidity, IP67 | Temperature and relative humidity | −30 to 60 °C; ±0.2 °C (0–60 °C), ±0.3 °C (−30 to 0 °C), ±2% RH | Not listed | Magnet | IP67; PC+ABS housing | Battery, about 10 years |
| No. 74 Room temperature & humidity sensor | Temperature and relative humidity | Not listed | ±2 %RH typical | Wall | Indoor; operates 5 to 50 °C | Battery |
| No. 75 Compact room temperature & humidity sensor | Temperature and relative humidity | −20 to 50 °C | ±0.3 °C typical; ±3 %RH typical (20 to 80 %RH) | Wall | IP52, indoor | Alkaline batteries |
| No. 76 Temperature & humidity sensor with probe port | Temperature and relative humidity; illuminance on the light-probe version | −40 to 80 °C | ±0.3 °C and ±3 %RH typical | Wall | Not listed | Lithium battery, about 10 years (manufacturer rating) |
| No. 77 Damp-room temperature & humidity sensor, IP67 | Temperature and relative humidity | −30 to 70 °C | ±0.3 °C (0 to 70 °C), ±0.6 °C (−30 to 0 °C); ±3 %RH (10 to 90 %RH), typical | Wall | IP67 | Lithium battery, about 10 years (manufacturer rating) |
| No. 79 Precision temperature & humidity probe | Temperature and relative humidity | −40 to 125 °C | ±0.1 °C (20 to 60 °C), ±0.2 °C (−40 to 90 °C); ±1.5 %RH (0 to 80 %), ±2 %RH (80 to 100 %) | Not listed | IP67; node operates −20 to 50 °C | Alkaline batteries, about 12.2 years (manufacturer rating) |
Doors and open/close contacts
All 7Radio: LoRaWAN (North America)
| Device | Reads | Range | Mount | Rating | Power |
|---|---|---|---|---|---|
| No. 28 Door contact, IP67 | Not listed | Not listed | Screw, adhesive or strap | IP67; −30 to 70 °C | Battery, about 10 years |
| No. 112 Outdoor dry-contact sensor | Dry-contact state, open count, last-open duration | Not listed | Not listed | IP67; −40 to 85 °C operating | 8,500 mAh lithium battery, about 5 years (manufacturer rating) |
| No. 113 Outdoor door & gate sensor | Open and close events | Up to 45 mm magnet gap | Wall; reed sensor on a 0.4 m cable | −40 to 85 °C operating | Lithium battery, about 5 years (manufacturer rating) |
| No. 114 Indoor door & window sensor | Open and close status | Up to 10 mm magnet gap | Screw or adhesive | Not listed | Battery (alkaline) |
| No. 115 Slim door & window contact | Open and close state | Up to 20 mm magnet gap | Adhesive | IP30 (indoor); −20 to 55 °C operating | Lithium battery |
| No. 116 Door & window contact with tamper alert | Open, close and tamper | Up to 20 mm magnet gap | Screw or adhesive | IP20 (indoor); −20 to 60 °C operating | Lithium battery, about 4 to 7 years (manufacturer rating) |
| No. 117 Two-channel open/close sensor | Open and close state | Up to 20 mm magnet gap | Magnet; contact on a 1 m cable | IP65; −20 to 55 °C operating | Lithium battery |
Specs from the Cognituv Connect catalog (October 2026). Where the catalog gives no value, the table says “Not listed”. Confirm site suitability, calibration and current product specifications before ordering. The product data sheet governs.
Process, rooms & cold chain in the catalog →Ask an engineer to compare for your site →